Comment Re:Indian Point == Ticking Timb Bomb (Score 5, Informative) 213
One unfortunate problem with nuke plants is that IIRC you have to have a continuous connection to the grid. If that connection fails, the plant has to scram to avoid damage to the generators (overspeed).
BS
Power stations (even non-nuclear) always have back-up generators that kick in on loss of grid to allow control of the plant to be maintained and for cooling pumps to take the heat out of the system in a controlled way. Generators will not overspeed if cut off the grid - their speeds are controlled by sophisticated control systems, and if they even fail then an old-fashioned back-up mechanical governor will cause the main steam supply valve to slam shut.
The plant would not be "scrammed" on loss of grid. Scramming means hitting a big red panic button. The plant would be kept spinning at first, obviously with the reactor power reduced to near zero, with residual heat being dumped through purposed heat exchangers and possibly releasing steam to atmosphere (unless it is a BWR - Indian Point is not), while the cause of the loss-of-grid was investigated - like getting the grid company on the phone. Many losses-of-grid are quite brief, but if it looked like it was going to be a while then the plant would be shut down in a controlled way, not by a scram button.