I chewed out a civil engineer exactly for this reason once. He placed an AC on my communication closet UPS. Granted...he had gone about upgrading the UPS to carry the AC.
What he didn't do was upgrade the UPS to 10x because of the inrush.
Sure, the UPS stayed on. The AC stayed on. The servers stayed on. Unfortunately the servers all crashed during the undervolt.
He was losing his goddamn mind. I'm like dude, just wire it to the mains. He insisted it was big enough. I pointed at the servers that had crashed out - those are the things you're trying to protect. You're protecting them so much that you're ruining them. Let the AC die for 30 minutes. We'll survive. If the system goes down due to thermals after 30 minutes, well it would have gone down due to UPS and generator power not working anyway.