Sure, the inverter/ATF is a Xantrex SW4048. The model has been replaced with other models. I've never had a problem with it, although I've heard some complaints about components in the newer models. The main service tie is a 30 amp 110 circuit, and there's a secondary input that I can drive with a generator or other 15 amp 110 source.
The batteries are Fullriver DC310-6 gel-packs which are supposed to deal with hydrogen out-gassing. I think the model number translates to 6 volt, 310 Amp hours. They're connected in series to yield 48 volts DC to the inverter.
The system was sized to run the critical circuits in the house for 3 days. (Critical being the heating boiler (LP), some lights, the kitchen (except the electric oven), a sump pump, and a circuit for the living room and master bedroom.